Modbus Adapter for PnP Bridge
This a README for the Modbus adapter on PnPBridge
Table of Contents
Adapter Configuration
The adapter configuration follows the format defined by Modbus Gateway configruation interface, an Azure PnP Interface. Follow the steps below to update config.json
to add a Modbus device to your PnPBrdige.
- Open
config.json
for the PnPBridge. - Add the following json payload to
Devices
. - Modify
deviceConfig
andinterfaceConfig
objects underDiscoveryParameters
to match your Modbus device configuration. Refer to following sections for more detailed descriptions of each field in these twoJSON
objects.
{
"_comment": "My Modbus Device",
"MatchFilters": {
"MatchType": "Exact"
},
"SelfDescribing": "true",
"PnpParameters": {
"Identity": "modbus-pnp-interface"
},
"DiscoveryParameters": {
"Identity": "modbus-pnp-discovery",
"deviceConfig": {
"unitId": 1,
"rtu": {
"port": "COM5",
"baudRate": "9600",
"dataBits": 8,
"stopBits": "ONE",
"parity": "NONE"
},
"tcp": null
},
"interfaceConfig": {
"interfaceId": "http://contoso.com/Co2Detector/1.0.0",
"telemetry": {
"co2": {
"startAddress": "40001",
"length": 1,
"dataType": "integer",
"defaultFrequency": 5000,
"conversionCoefficient": 1
},
"temperature": {
"startAddress": "40003",
"length": 1,
"dataType": "decimal",
"defaultFrequency": 5000,
"conversionCoefficient": 0.01
}
},
"properties": {
"firmwareVersion": {
"startAddress": "40482",
"length": 1,
"dataType": "hexstring",
"defaultFrequency": 60000,
"conversionCoefficient": 1,
"access": 1
},
"modelName": {
"startAddress": "40483",
"length": 2,
"dataType": "string",
"defaultFrequency": 60000,
"conversionCoefficient": 1,
"access": 1
},
"alarmStatus_co2": {
"startAddress": "00305",
"length": 1,
"dataType": "boolean",
"defaultFrequency": 30000,
"conversionCoefficient": 1,
"access": 1
},
"alarmThreshold_co2": {
"startAddress": "40225",
"length": 1,
"dataType": "integer",
"defaultFrequency": 30000,
"conversionCoefficient": 1,
"access": 2
}
},
"commands": {
"clearAlarm_co2": {
"startAddress": "00305",
"length": 1,
"dataType": "flag",
"conversionCoefficient": 1
}
}
}
}
}
DeviceConfig
DeviceConfig provides the physical connection information between the Modbus gateway and the Modbus edge devices. This part of configuration provides TCP/IP or serial connection information (must pick either one). You may provide null
value for the connection you do not use.
"deviceConfig": {
"unitId": 1,
"rtu": null,
"tcp": {
"host": "192.168.1.111",
"port": 502
}
}
Configuration Definition:
Field | Data Type | Description |
---|---|---|
unitId |
integer | The id (or slave address) of the Modbus device |
rtu |
||
port |
integer | Serial port name, ex: "/dev/ttys0" or "COM1". |
baudRate |
string | Baud rate of the serial port. Valid values: ..."9600", "14400", "19200"... |
dataBits |
integer | Data Bit for the serial port. Valid values: 7 and 8 . |
stopBits |
string | Stop Bit used for the serial port. Valid values: "ONE", "TWO", "OnePointFive". |
parity |
string | Serial port parity. Valid values: "ODD", "EVEN", and "NONE". |
tcp |
||
host |
string | Ipv4 address of the Modbus device |
port |
integer | Port number of the Modbus device |
interfaceConfig
Interface Configuration provides a mapping of Modbus device's memory addresses to P&P interfaces. This sample configuration is based on the schema of a sample CO₂ detector. The interfaceId and capability names provided here should match those of device interfaces schema.
"interfaceConfig": {
"interfaceId": "http://contoso.com/Co2Detector/1.0.0",
"telemetry": {
"co2": {
"startAddress": "40001",
"length": 1,
"dataType": "integer",
"defaultFrequency": 5000,
"conversionCoefficient": 1
},
"temperature": {
"startAddress": "40003",
"length": 1,
"dataType": "decimal",
"defaultFrequency": 5000,
"conversionCoefficient": 0.01
}
},
"properties": {
"firmwareVersion": {
"startAddress": "40482",
"length": 1,
"dataType": "hexstring",
"defaultFrequency": 60000,
"conversionCoefficient": 1,
"access": 1
},
"modelName": {
"startAddress": "40483",
"length": 2,
"dataType": "string",
"defaultFrequency": 60000,
"conversionCoefficient": 1,
"access": 1
},
"alarmStatus_co2": {
"startAddress": "00305",
"length": 1,
"dataType": "boolean",
"defaultFrequency": 30000,
"conversionCoefficient": 1,
"access": 1
},
"alarmThreshold_co2": {
"startAddress": "40225",
"length": 1,
"dataType": "integer",
"defaultFrequency": 30000,
"conversionCoefficient": 1,
"access": 2
}
},
"commands": {
"clearAlarm_co2": {
"startAddress": "00305",
"length": 1,
"dataType": "flag",
"conversionCoefficient": 1
}
}
}
Configuration Definition:
Field | Data Type | Description |
---|---|---|
interfaceId |
string | The interfaceID of the Modbus device. This should map the device type of the Modbus devices listed in deviceMap.json |
Capability Definition |
||
startAddress |
integer | Starting address of the Modbus device to read from |
length |
integer | Number of bytes to read. |
dataType |
string | Data type that the raw Modbus response should convert to. Valid values: "integer" , "decimal" . Experimental Data Types*: "string" : returns Modbus byte array as ASCII string. "hexstring" : return Modbus byte arry as hexadecimal string. |
defaultFrequency |
integer | For telemetry and property capability only. The time interval (in miliseconds) between each data pull from the Modbus device. |
conversionCoefficient |
decimal | The coefficient that the raw Modbus response should multiply to to get actual value. It is 1 by default. Ex. If the raw response of the temperature (in Celcius) reading from the Modbus device is 0x0935 (=2357 ), we need to mutiply the raw data to 0.01 to get the actual value (23.57 ) in Celcius. 0.01 is the conversionCoefficient . |
access |
integer | For property capability only. 1 for read-only property 2 for writable property |
* We understand that data type like "string" can be interpreted differently for each device manufacturer as Modbus does not provide a standard representation for "string". Please share your opnion on how these type of data should be generally converted
Reference
Modbus
A serial communication protocol that is commonly used in the industrial IoT world. This module supports two most common variants of the Modbus protocols: Modbus TCP/IP (communicates over TCP/IP networks) and Modbus RTU (communicates over RS485 connection).